Nonlinear Load, THDi, THDv, Transformer RMS Current, Harmonic Heating, Neutral Exposure, Short-Circuit Strength & Filter Effect

Shipboard Power Quality, Harmonic Load & Transformer Capacity Tool

Screen whether added nonlinear shipboard loads fit the transformer without hiding harmonic current behind ordinary kVA. Simple mode combines active/reactive load, added THDi and the entered post-retrofit bus THDv. Advanced mode builds the nonlinear load package row by row, applies filter reductions, estimates RSS and arithmetic worst-case harmonic current, checks transformer derating, neutral triplen exposure, bus voltage distortion and source short-circuit strength.

Data type
↑
Need filter, spectrum or neutral-current detail? Click Advanced above.Add each converter/load with demand factor, PF, THDi, filter reduction and triplen share. Advanced also adds transformer harmonic derating, short-circuit strength and a measured/predicted 5th/7th/11th/13th voltage-harmonic spectrum.

Fast Transformer & Distortion Screen

Simple mode does not calculate bus THDv from THDi. Enter a measured/predicted post-retrofit THDv from the power-quality study or vendor/system-integrator analysis.

V, three-phase.
kVA.
kW.
kW at the screened operating condition.
% of added load fundamental current.
Measured/predicted %, not calculated here.
Use the approved vessel/project limit.
% of nameplate kVA.

Transformer & System Basis

V, three-phase.
kVA.
%.
% from manufacturer/project harmonic study.
kW.
MVA at the screened bus, from fault/system study.
%.
%.
A, only used for 4-wire systems.

Nonlinear Load Register

THDi is entered per load. Filter reduction acts on THDi before aggregation. RSS aggregation is used for the primary screening result; an arithmetic-sum current is also shown as a conservative no-cancellation bound.

Nonlinear loadQtyRated kW / unitDemand %PFTHDi %Filter reduction %Triplen share of harmonic current %

Bus Voltage Harmonic Spectrum

Enter measured/predicted voltage harmonic magnitudes as % of fundamental. These are not derived from the load THDi register because accurate THDv requires network impedance by harmonic order.

%.
%.
%.
%.

Power-Quality Readiness

Power-quality screening only: this tool does not replace a harmonic load-flow / impedance study, transformer thermal analysis, resonance study, protection review, EMC assessment or class approval. THDv must come from measurement or a proper network calculation. Harmonic-current aggregation here is a screening approximation and does not model harmonic phase angle or cancellation.