Marine Cooling Water & Heat Exchanger Tool
Marine Cooling Water & Heat Exchanger Tool
Screen a marine central cooler from the heat load all the way to seawater flow, plate area, fouling reserve and pump demand. Simple mode sizes the duty and checks installed area. Advanced combines equipment heat loads with multiple cooler units, availability, clean U-value, fouling resistance, seawater-flow capacity, pressure drop and warm-sea sensitivity.
Cooling Duty
Central Cooling Temperature Basis
Heat Load Register
Use OEM heat-rejection data where available. Duty factor lets you represent the present operating condition without changing the equipment design load.
| Use | Equipment / circuit | Design heat kW | Current duty % |
|---|
Central Cooler Register
Uclean and fouling resistance are entered separately. Effective U is calculated from 1/Udirty = 1/Uclean + Rf. Rated seawater flow and pressure drop are used for a parallel-flow capacity and pump-head screen.
| Use | Available? | Area m² | Clean U W/m²K | Rf m²K/W | Rated SW flow m³/h | Rated ΔP kPa |
|---|