Ship Universe Marine Electrical Quality Tool

Shipboard Power Quality, Harmonic Load & Transformer Capacity Tool

Turn shipboard nonlinear loads into a transformer and distribution-bus capacity screen. Model fundamental and harmonic RMS current, user-entered transformer derating, neutral current from triplen harmonics, measured voltage distortion, load losses, active-filter sizing and the point where a power-quality problem becomes a capacity problem.

Currency selector changes display only. No exchange-rate conversion is performed.

Bus & Transformer

Use the transformer or distribution transformer actually carrying the modeled load group.

V
kVA
%
Use an OEM, design-office or project derating factor. The tool does not invent a transformer derating curve.
% usable capacity
A

Linear & Nonlinear Loads

kW
%
kW
%
% of I1
%
Used to estimate balanced 3-phase, 4-wire neutral current.

Measured Power Quality

%
%
%
%
%
User-entered project limit for screening. It is not a built-in regulatory threshold.

Loss & Mitigation Economics

kW
hours/year
$ /kWh
A
%
$
$
$

Load Groups

Build the fundamental load from actual demand groups. Harmonic current is entered separately in the spectrum table.

Use Load Group kW PF Demand %

Bus Harmonic Spectrum

Enter each harmonic current as a percentage of total bus fundamental current I1. Triplen orders are automatically included in the neutral-current screen.

Use Harmonic Order Current % of I1

Bus, Transformer & Measured Quality

V
kVA
%
%
A
%
%
%
%
%

Loss & Mitigation Economics

kW
hours/year
$ /kWh
A
%
$
$
$
Engineering note: transformer harmonic capacity is not derived from THDi alone. This tool keeps nameplate capacity, user-entered harmonic-service derating, RMS current, harmonic spectrum and K-factor demand separate so a screening result does not masquerade as an OEM thermal rating.
Enter bus, load, harmonic and transformer assumptions to build the power-quality capacity screen.
Electrical engineering screening only. Harmonic behavior depends on source impedance, transformer design, generator characteristics, converter topology, load diversity, cable impedance, resonance, capacitor banks, filter tuning, grounding, phase loading and operating mode. K-factor demand is a spectrum indicator, not an automatic transformer rating or derating instruction. Neutral-current modeling assumes a balanced 3-phase, 4-wire system for triplen harmonics, and post-filter neutral current assumes the entered harmonic reduction acts proportionally on the triplen content. Current-related transformer loss is a simplified I²-based estimate and does not separately model frequency-dependent eddy or stray losses. Measured THDv and voltage-unbalance limits are user-entered planning criteria. Validate equipment loading, protection, cable ampacity, harmonic compliance and mitigation design using power-quality measurements, short-circuit and harmonic studies, transformer OEM data and the vessel's approved electrical design.
Generated by ShipUniverse.com
Results copied
By the ShipUniverse Editorial Team — About Us | Contact