Synchronizing • Breaker Closing Compensation • Reverse Power • Load Transfer • Generator Protection • PMS Readiness

Marine Generator Synchronizing, Reverse Power & Load Transfer Protection Tool

Screen live-bus generator synchronization using voltage, frequency, phase angle and breaker response time, then extend the analysis to reverse-power protection and controlled generator load transfer. Advanced mode models multiple generators, synchronizing attempts and transfer events without replacing the vessel's synchronizer, protection relay, PMS logic or approved settings.

Figures represent
↑
Simple is intentionally a fast live-bus synchronization screen. Reverse-power and load-transfer protection are handled in Advanced mode because they require generator rating, relay settings and transfer timing. Closing authorization remains with the installed synchronizer / sync-check relay and vessel procedure.
VoltageGenerator-to-bus mismatch
SlipFrequency and phase drift
BreakerPredicted contact angle

Live-Bus Synchronizing Snapshot

V line-line.
V line-line.
Hz.
Hz. Positive slip means generator is faster.
Degrees relative to bus. Positive = leading.
ms from close command to main-contact touch.
±% user-entered sync-check window.
±Hz user-entered sync-check window.
±° user-entered closing window.

Bus & Synchronizer Settings

±% user-entered sync-check limit.
±Hz.
±°.
% of generator rated kW per second. User planning threshold.

Generator / Reverse-Power Protection Register

Enter actual relay settings from the vessel. Reverse power is shown as negative active power. The tool does not change or recommend relay settings.

Use Generator Prime mover Rated kW Current kW Reverse trip % rated Trip delay s Breaker opening time ms Available?

Synchronizing Attempt Register

Each row predicts phase angle at breaker-contact touch if a close command is issued at the entered present angle. The ideal command angle compensates for the entered breaker closing time and slip frequency.

Use Attempt Generator Gen V Gen Hz Phase now ° Breaker close ms Method Sync-check enabled?

Load Transfer / Breaker Opening Register

The transfer model is linear by design. It screens whether an unloading ramp could cross the entered reverse-power threshold before the breaker physically opens.

Use Event Generator Start kW Target kW Ramp time s Open command at kW Observed reverse duration s

Protection / Commissioning Checks

Protection boundary: this tool is an engineering screen, not a synchronizing or protection relay. Actual breaker-close permissives, reverse-power pickup/delay, generator protection, PMS logic, reactive-power sharing and class/flag acceptance remain controlled by the installed approved system and vessel procedures. Never bypass a sync-check or protective interlock based on this calculation.