Ship Motor Starting Current, Voltage Dip & Generator Capacity Tool

Starting Current • Bus Voltage Dip • Locked-Rotor kVA • Generator Transient Strength • Start Sequencing • N-1 Capacity

Ship Motor Starting Current, Voltage Dip & Generator Capacity Tool

Screen shipboard motor starts against the actual generator bank instead of comparing motor kW with generator kW. Simple mode estimates starting current, locked-rotor kVA, initial bus-voltage dip and generator requirement. Advanced models multiple motors, start overlap, multiple generator sets, equivalent subtransient source strength, N-1 operation, voltage-squared torque retention and start-sequence risk.

Figures represent
↑
Eight inputs, focused on the start that stresses the bus.The allowable voltage dip is deliberately user-entered. Class, OEM, starter, contactor and vessel-specific requirements remain controlling.
MotorStarting amps & kVA
BusInitial voltage dip
GenerationCapacity & reserve

Motor Start

A at rated voltage.
V line-to-line, 3-phase.
Locked-rotor / limited-start current ÷ rated current.
Use motor/starter data where available.

Generator Bank

Total online generator kVA.
% on the online-bank base. Use OEM transient/subtransient data.
% of online kVA, modeled at 0.85 PF.
% user-entered project/class/OEM criterion.

System Limits & Starting Study

% user-entered.
% of online bank kVA.
% user-entered contingency screen.

Generator Register

Equivalent source strength is calculated from each online generator's kVA and entered Xdʺ. Pre-start load is shared in proportion to online kVA.

UseAvailable?NameRated kVAXdʺ %Pre-start load %

Motor Starting Sequence

Start time and acceleration duration allow overlapping starts. Enter the effective starting-current multiple produced by the actual starter. The method label is descriptive; the entered current multiple controls the calculation.

UseMotor / loadkWRated ARun PFMethodStart × FLAStart PFStart at sAccel sMin bus V %Essential?

Study / Protection Checks

Engineering boundary: the transient-voltage model is a planning/screening calculation using generator subtransient source impedance and starting loads represented as voltage-dependent impedance. It does not replace OEM dynamic generator/AVR simulation, class approval, short-circuit studies, protection coordination or a measured vessel starting test.