Fixed CO₂ Fire-Extinguishing Cylinder Quantity, Flooding Concentration & Release Time Tool
Screen a shipboard high-pressure fixed CO₂ system from protected-space volume through statutory free-gas quantity, required cylinder count, installed charge margin, nominal flooding concentration, discharge-time capability, pre-release alarms, controls and service readiness. The tool separates the FSS quantity calculation from the approved hydraulic design and the operational release procedure.
Vessel & System Basis
Use the vessel's approved fire-control plan, system drawings and class/flag-approved design values. Do not substitute a generic volume percentage where the approved arrangement, ship type or protected-space rule is more specific.
Protected Space & Quantity Basis
Advanced Protected-Space Register
Where one CO₂ bank protects more than one space, the FSS Code generally permits the available quantity to be based on the largest single requirement, provided the approved selector-valve arrangement directs the agent correctly. Each row below is screened independently and the largest requirement governs the common bank.
| Space | Category | Reduced vol m³ | Full vol m³ | Air receiver m³ | Custom % | Required kg | Req. cylinders | Release basis |
|---|
Installed Cylinder Bank & Charge Condition
Release Capacity & Flooding Time
The tool calculates the average mass-flow rate needed to satisfy the applicable FSS discharge-time requirement. Use the approved hydraulic calculation or manufacturer/class documentation for actual nozzle, pipe, manifold and orifice sizing.